Diagnostics 35
Test Mode
In this mode the control can be put through a performance test to verify the operation of the control’s components and software.
Switching DIP#1 on from “R” (run) to “T” (test) enters Test Mode. When entering Test Mode, all current program settings, DIP
switch settings and statistical data are saved. When exiting test mode, the valve will home itself. The test sequence is shown in
the table below.
User Action Desired Result Functionality Tested
Switch DIP#1 on All LCD segments on DIP switch #1 and Test Mode Entry
Press any button Software version displayed (ERRSUM
displayed if software integrity check fails)
Software Integrity check
Press any button Blank Display (unless devices connected) Exit Software Integrity check
The actions below can be done in any sequence
Switch DIP#2 on Display to show “2” DIP switch #2 input
Switch DIP#2 off “2” disappears
Repeat for each DIP#3-10 Display to show corresponding DIP
number
DIP switch inputs
Press PROGRAM button Display to show “11” and run motor for
15 seconds
PROGRAM button input and motor
output
Press UP button Display to show “12” UP button input
Press DOWN button Display to show “13” DOWN button input
Press REGEN button Display to show “14” REGEN button input
Press INFORMATION button Display to show “15” (“EE” displayed if
EEPROM memory check fails)
INFORMATION button input and
EEPROM memory check
Close “Home” Cam Switch Display to show “H” “Home” Cam Switch input
Open “Home” Cam Switch “H” disappears
Close “Position” Cam Switch Display to show “P” “Position” Cam Switch input
Open “Position” Cam Switch “P” disappears
Connect Flow Meter Display to show “gpm” icon when
connected
Flow Meter ‘Detect’ input
Provide flow pulses “gpm” icon flashes when pulses are
present
Flow Meter ‘Signal’ input
Connect Aqua-Sensor Simulator Device
or Probe (probe must be in the resin bed)
Display to show “REGEN” icon when
connected and “OK” if Aqua-Sensor
circuitry is operating within proper range
Aqua-Sensor ‘Detect’ input and Digital
Aqua-Sensor circuitry check
“Balance” Aqua-Sensor Simulator Device “REGEN” icon to stop flashing within
30 seconds and “OK” indication should
remain
Aqua-Sensor ‘Signal’ input
“Unbalance” Aqua-Sensor Simulator “REGEN” icon to flash within 30 seconds
and “OK” indication should remain
When exiting test mode, if the dip switches or sensors have not changed, the control is to restore all values from EEPROM. If the
dip switch or sensors have changed the values should reset to factory defaults. In either case the valve will home itself.
Note: Device connections and DIP settings before entering Test Mode. Upon exiting test mode, if a device connection or DIP
switch setting is different from when Test Mode was entered, the control’s program settings will default accordingly.